Table Losses same for all







Cotrolled OD SDR 21 thermoplastic pipe.


















PRESSURE LOSS














C = 150






200psi PR SDR 21 PVC PIPE














Pipe Sizes: Nominal                                                                                                                     Losses per 100 ft: lb/in2
gpm 1/2 in(1) 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in gpm 2 in 2-1/2 in 3 in 4 in 6 in 8 in
1 0.248 0.067 0.020 0.006 0.003 0.001 105 5.92 2.32 0.885 0.260 0.040 0.011
2 0.896 .243 .072 .023 .012 .004 110 6.45 2.53 0.964 .284 .043 .012
3 1.90 .515 .152 .048 .025 .008 115   2.74 1.05 .308 .047 .013
4 3.23 0.876 .259 .082 .042 .014 120   2.97 1.13 .333 .051 .014
5 4.88 1.32 .391 .123 .063 .021 125   3.20 1.22 .359 .055 .015
6 6.84 1.86 .548 .173 .089 .030 130   3.44 1.31 .386 .059 .016
7 9.09 2.47 .729 .230 .118 .039 135   3.69 1.41 .414 .063 .017
8 11.64 3.16 0.934 .294 .151 .051 140   3.95 1.51 .443 .068 .019
9 14.48 3.93 1.16 .366 .188 .063 145   4.21 1.61 .473 .072 .020
10 17.59 4.77 1.41 0.445 0.228 0.076 150   4.48 1.71 0.503 0.077 0.021
11 20.98 5.69 1.68 .531 .272 .091 160   5.05 1.93 .567 .086 .024
12 24.65 6.69 1.98 .623 .320 .107 170     2.16 .634 .097 .027
13   7.75 2.29 .723 .371 .124 180     2.40 .705 .108 .030
14   8.89 2.63 .829 .425 .142 190 10 in   2.65 .779 .119 .033
15   10.11 2.99 0.942 .483 .162 200 0.012   2.91 .857 .131 .036
16   11.39 3.37 1.06 .544 .182 210 .014   3.19 0.938 .143 .040
17   12.74 3.77 1.19 .609 .204 220 .015   3.48 1.02 .156 .043
18   14.16 4.19 1.32 .677 .226 230 .016   3.77 1.11 .169 .047
19 2-1/2 in 15.65 4.63 1.46 .748 .250 240 .017   4.08 1.20 .183 .051
20 0.108 17.21 5.09 1.60 0.823 0.275 250 .019     1.29 0.197 0.055
22 .129   6.07 1.91 0.981 .328 260 .020     1.39 .212 .059
24 .151   7.13 2.25 1.15 .386 270 .022     1.49 .228 .063
26 .175   8.27 2.61 1.34 .447 280 .023     1.60 .244 .067
28 .201   9.48 2.99 1.53 .513 290 .025 12 in   1.70 .260 .072
30 .228   10.77 3.40 1.74 .583 300 0.026 0.011   1.81 .277 .076
32 .257   12.14 3.83 1.96 .657 325 .030 .013   2.10 .321 .089
34 .288   13.58 4.28 2.20 .735 350 .035 .015   2.41 .368 .102
36 .320     4.76 2.44 .816 375 .040 .017   2.74 .418 .116
38 .354 3 in   5.26 2.70 .902 400 .045 .019   3.09 .471 .130
40 0.389 0.148   5.78 2.97 0.992 425 .050 .022     .527 .146
42 .426 .162   6.33 3.25 1.09 450 .055 .024     0.586 0.162
44 .464 .177   6.90 3.54 1.18 475 .061 .027     .647 .179
46 .504 .192   7.49 3.84 1.28 500 0.067 0.029     .712 .197
48 .545 .208   8.10 4.15 1.39 550 .080 .035     .849 .235
50 .588 .224   8.74 4.48 1.50 600 .094 .041     0.997 .276
52 .632 .241   9.39 4.82 1.61 650 .110 .048     1.16 .320
54 .677 .259   10.07 5.17 1.73 700 .126 .055     1.33 .367
56 .725 .277     5.53 1.85 800 .161 .070     1.70 .470
(1) 1/2 in SDR 21 not standard. For convenience, losses for SDR 13.5 listed.
















POLY VINYL CHLORIDE (PVC) PLASTIC PIPE






Pressure loss tables are provided for both SDR-PR and





Schedule Wall PVC pipe.























Unlike many pipes, the standard wall thickness of PVC





pipe has a plus tolerance only, ranging from 0.020 in to





0.090 in. Many pressure loss tables use the standard





minimum wall (without tolerances) for computation purposes.




Since maufacturing processes preclude







achievement of this thickness, most all PVC pipe will





have a thicker wall and consequently a smaller ID.






Accordingly, use of the standard wall to prepare loss






tables is not realistic. The loss tables here use





a wall thickness which includes one-half of the tolerances.





This results in a more realistic average ID. This






method of determining ID for calculation of pressure






losses is recommended by the Plastic Pipe Institute (PPI).



















Caution should be exercised to control velocities in PVC





pipe to avoid damage from pressure surging (water hammer).

















Note: PVC pressure loss tables can be used for any






controlled OD thermoplastic pipe of the same SDR or





Schedule number.











Free shipping and discounted pricing may be available in your area!

What US zip code are you shipping to?

does not apply to orders outside the United States